Electrical Specifications

Power Requirements: 24VDC nominal (18 to 32VDC range)

Power Consumption: 3VA (3 Watt) Max

Signal Outputs: +4 to 20mA, Digital RS485 Modbus, Relays.
*All Relays Contact Rating 1 Amp@125VAC/30VDC

Factory Default Relays Settings:
•Fire Relay: Normally Open, Closed on Fire Detection, Non-Latching
•Fault Relay: Normally Closed, Open on Fault Detection, Non-Latching

Performance Specifications

Detection Response Time: 1 to 2 seconds

Detection Distance: Up to 100ft (30m) depending on detected fuel.

Detection Field of View: Up to 90° (45° Left/Right of center)

Mechanical Specifications

Ingress Protection: IP66

Operating Temperature: ‐40°F to +185°F (‐40°C to 85°C)

Storage Temperature: ‐76°F to +185°F (‐60°C to 85°C)

Humidity Range: 0 to 98% relative humidity (can withstand 100% condensing humidity for short periods of time)

Conduit Connection: Two (2) M20 X 1.5, adaptable to ¾” NPT

Enclosure Material: Stainless Steel (Grade 316) or Aluminum (coated)

Dimensions: 9.08″X 14.20″X 3.94″ (231mm X 361mm X 100mm) mounted with bracket

Weight: Stainless Steel 13.2lb (6.0kg), Aluminum 7.7lb (3.5kg)

  • Refineries, bulk terminals, and tank farms
  • Compressor stations and pipeline facilities
  • Power plants and gas turbine facilities
  • Transportation facilities (airports and subways)
  • Oil and gas fired boilers/furnaces
  • Aircraft hangars
  • Paint Booths

ITES Test Lamp

Simulates fire signal on our IPES detectors to test alarm response in the field without removing detectors from the application.

Protective Visor

Protects the flame detector from rain and direct sunlight which can damage the optics.

Magnetic Collar

Disables signal outputs during flame/functional testing.

Mounting Bracket

Swivel mounting bracket offers an easy installation solution to mount IPES Flame detectors, a tilt of up to +/-45 degrees in the vertical plane.

Vortex Air Shield

Keeps airborne particles away from the detector and optical window on our IPES Flame Detectors.