Vector-Oxygen

Electrical Specifications

Power Requirements: +24VDC Nominal (+18 to 32VDC)

Power Consumption: 4.3 W-standby; 5.3 W-during alarms; 12.0 W-w/ heater on (temp ≤ 30°F)

Signal Output From Vector FCU: 2X +4-20mA analog output, Digital RS-485 Modbus RTU, Relays, HART

Alarm Relays:
3 User Programmed Alarm Relays (factory default setting: NO)
1 Fault Condition Programmed Relay (factory default setting: NC)

Mechanical Specifications

Ingress Protection: IP66/67

Operating Temperature: -58°F to +167°C (-50°C to +75°C) -76°F to +167°C (-60°C to +75°C) with heater enabled

Storage Temperature: -76°F to +185°C (-60°C to +85°C)

Humidity Range: 0 to 100% relative humidity, non condensing

Conduit Connection: ¾” NPT
2 connections for Sensors
2 connections for Field Wiring

Enclosure Material: Stainless Steel (Type 316L) or Aluminum

Dimensions: 7.50” x 5.60” x 4.28″ (190.5mm x 142.24mm x 108.71mm)

Weight: Vector with one PGU attached – 14.00 lbs (6.35 kg)

  • Freezer chemical storage areas
  • Prototyping and welding buildings
  • General buildings
  • Controlled labs for critical processes
  • Analyzer rooms
  • Confined rooms or areas.
magwand

Magnetic Wand

Used for accessing display settings and perform calibrations.

PGU-Protective Cover

Offers sensor protection against water and dust intrusion.

PGU Calibration Cup

Used in the PGU calibration.

calkit

Calibraiton Gas Kit

Gas Kit includes two gas cylinders, regulator, 36” length of clear flex tubing, carrying case.

Oxygen Detection Range: 0-30%v//v


Visit our Customer Center for product resources

 

VECTOR-OXYGEN RESOURCES

Contact Us / Find a Rep
+1.408.886.9746